CUMMINS POWER GENERATION GENERATOR SET 2015: ELECTRICAL SYSTEM:WIRING
NHTSA Campaign ID Number: 18V504000
Make | Model | Year |
---|---|---|
CUMMINS POWER GENERATION | GENERATOR SET | 2015 |
Date Owners Notified | Date Received by ODI | Date Added to Database |
2018-09-21 | 2018-07-31 | 2018-08-07 |
Production Dates: 2015-09-15 - 2018-07-20
Manufacturers Involved: Cummins, Inc.
Component: ELECTRICAL SYSTEM:WIRING
Potential Number Of Units Affected: 921
Report Initiator: MFR MFR Report
Cummins Inc. "Cummins" is recalling certain 2015-2018 Power Generation trailers, models C60D6R, C150D6R, C80D6R, C100D6R, C200D6R, C300D6R, C150D2R3 and C200D2Re, 2016-2018 C275D2Re and 2018 C70D2Re and C100D2Re. These generator sets may have incorrectly wired remote emergency stop and remote start connections causing the remote stop to not function and shut down the generator as intended.
If the unit does not shut down as expected when the remote E-stop is activated, it can increase the risk of injury.
Cummins will notify owners, and dealers will inspect the remote E-stop function and, if necessary, repair or replace the remote E-stop/remote start switch panel, free of charge. The recall is expected to begin September 2018. Owners may contact Cummins customer service at 1-800-286-6467.
Owners may also contact the National Highway Traffic Safety Administration Vehicle Safety Hotline at 1-888-327-4236 'TTY 1-800-424-9153', or go to www.safercar.gov.